- High-resolution colour display for the graphic representation of your measurement data
- Extended measurement menus – such as gas pipe testing – for a comprehensive analysis of your heating system
- Logger function for easy long-term recording of the measurement curve
- Graphic processing of measurement data
- Instrument diagnosis function uses easy „traffic light’’ presentation to enable comprehensive instrument diagnosis
- Pressure measurement up to 300 mbar
- User-defined fuels
- Powerful memory management: 500,000 readings
- USB interface for data readout to a PC software
- ZIV (Central Guild Association) driver for all standard industry software packages
Testo 330-2 LL Flue Gas Analyser Pro Set with printer – (0563 3372 71)
£2,088.90
Description
Testo 330-2 LL – Flue Gas Analysers
With long-life gas sensors, battery, charger, graphic display, Flue gas probe (300mm x 8mm), carry case.
Memory | 500.000 readings |
---|---|
Display | Colour graphic display with 240 x 320 Pixel |
Storage temperature | -20 to +50 °C |
Operating temperature | -5 to +45 °C |
Weight | 600 g |
Dimensions | 270 x 90 x 65 mm |
Probe – Type K | |
---|---|
Meas. Range | -40 to +1200 °C |
Resolution | 0.1 °C (-40 to 999,9 °C)
1 °C (remaining range) |
Probe – CO | |
Meas. Range | 0 to 500 ppm |
Accuracy | ±5 ppm (0 to 100 ppm)
±5% of mv (>100 ppm) |
Resolution | 1 ppm |
Response time | Approx. 35 s |
Probe – CO2 | |
Meas. Range | 0 to 1 Vol. %
0 to 10.000 ppm |
Accuracy | ±(50 ppm ±2% of mv) (0 to 5000 ppm) |
Response time | Approx. 35 s |
Probe – Differential pressure | |
Meas. Range | 0 to 300 hPa |
Accuracy | ±0.5 hPa (0.0 to 50.0 hPa)
±1% of mv (50.1 to 100.0 hPa) ±1.5 % of mv (remaining range) |
Resolution | 0.1 hPa |
Probe – Draught measurement | |
Meas. Range | -9.99 to +40 hPa |
Accuracy | ±0.02 hPa or ±5% of mv (-0.50 to +0.60 hPa)
±0.03 hPa (+0.61 to +3.00 hPa) ±1.5% of mv (+3.01 to +40.00 hPa) |
Probe – Exhaust gas loss measurement | |
Meas. Range | 0 to 99.9% |
Resolution | 0.1% |
Probe – Electrochemical measurement CO | |
Meas. Range | 0 to 4000 ppm |
Accuracy | ±20 ppm (0 to 400 ppm)
±5% of mv (401 to 1000 ppm) ±10% of mv (1001 to 4000 ppm) |
Resolution | 1 ppm |
Probe – Electrochemical measurement NO (only applicable with NO upgrade sensor as optional extra) |
|
Meas. Range | 0 to 3000 ppm |
Accuracy | ±5 ppm (0 to 100 ppm)
±5% of mv (101 to 2000 ppm) ±10% of mv (2001 to 3000 ppm) |
Resolution | 1 ppm |
Probe – Electrochemical measurement O2 | |
Meas. Range | 0 to 21 Vol. % |
Accuracy | ±0.2 Vol. % |
Resolution | 0.1 Vol. % |
Probe – Efficiency Measurement (Eta) | |
Meas. Range | 0 to 120% |
Resolution | 0.1% |
Probe – CO2-determination | |
Meas. Range | 0 to CO2 max |
Accuracy | ±0.2 Vol. % |
Reaction time t90 | < 40 s |
Reviews